Correct running of pneumatic equipments in industrial processes depends, most of cases, on steady and safe feed, i.e. feed realized by
air being continuously pressure controlled and filtered too.
Domizi Snc included in their products range also the Filter 970, and in order to extend application possibilities, they produce it in two
different versions, with outer chamber in Carbon steel, and in Stainless steel AISI 304; both versions can be fixed on the same line of
air pipe, or on a wall thanks to L bracket, or fixed on the back of a panel :
as described below.
Filter. Air is filtered by a cartridge made in sintered stainless steel, easy
to be restored and replaced. Its chamber is provided with drain valve to
take away the oil condensate present in feeding air.
Adjustment. The outgoing air pressure is kept steady by a diaphragm
controlled by a load spring and by a pilot valve; the adjustment of this
pressure is realized by acting on the screw loading the spring.
Operation range. The Filter 970 can accept inlet air with pressure up to
150 psi (10,5 bar), and is available in 3 different outlet pressures :
0÷30
psi (0÷2,1 bar), 0÷60 psi (0÷4,2 bar), 0÷100 psi (0÷6,6 bar).
The instrument, when adjusted at 20psi (1,4 bar) and feeded at 100psi (7
bar), assures a flow of 20 Nm³/h.
Connections.
The Filter 970 has 4 threaded holes ¼” NPT-F, placed at
90° on the central body. The inlet air hole is marked E, while the
remaining 3 outlet holes are marked U and may be connected to 3 users,
or to 2 users + 1 manometer.
When not used, the outlet U holes shall be kept plugged by the socket
head screws delivered on issue.
Manometer. Upon request, the Filter 970 can be supplied together with
a Ø50mm manometer for the outlet pressure.
|